TM 9-6115-659-13&P
NOTES:
1. REMOVE BRAID FROM FOUR GROUND WIRES (12 AWG). TWIST TOGETHER AND INSTALL TERMINAL LUG,
FIND NO. 4, AS SHOWN. TERMINAL SHALL BE INSTALLED IN ACCORDANCE WITH MIL-STD-454,
REQUIREMENT 19.
2. AT PIGTAIL END OF CABLE, THE FOUR 12 AWG GROUNDING CONDUCTORS SHALL BE TWISTED
TOGETHER, STARTING AT THE JACKET. CONDUCTORS SHALL BE SOLDER COATED FOR A LENGTH OF .25
FROM END USING SOLDER, FIND NO. 8.
3. AT PIGTAIL END OF CABLE, EACH INSULATED CONDUCTOR SHALL BE STRIPPED 1.25 FROM END AND
HAVE THEIR INDIVIDUAL STRANDS TWISTED TOGETHER. SOLDER COAT FOR A LENGTH OF .12 FROM
RND USING SOLDER, FIND NO. 8.
4. INSULATION COLORS, IN ACCORDANCE WITH WIRE LIST, SHALL BE INCLUDED AS PART OF THE
ORDERING DATA.
5. HOT STAMP 97403-13228F5836- WITH APPROPRIATE DASH NO., AND W- IN .23-.39 HIGH CHARACTERS ON
INSULATION SLEEVING, FIND NO. 5, IN ACCORDANCE WITH MIL-M-60903.
6. HOT STAMP WITH TERMINAL DESIGNATION, AS SHOWN ON WIRE LIST, USING. 12-.22 HIGH CHARACTERS,
IN TWO PIACES APPROXIMATELY 180° APART ON INSULATION SLEEVING, FIND N0.6AND7,IN
ACCORDANCE WITH MIL-M-60903.
Figure G-5. Cable Assembly W1 and W2 (Sheet 2).
G-12