ARMY TM 9-6115-604-12
NAVY NAVFAC P-8-633-12
Table 1-1. System Capacities and Detailed Data on Components (Continued)
9. CONTROLS, INSTRUMENTS, AND SWITCHGEAR (CONTINUED)
AC KILOVARS Meter M108
Drawing Number:
80-7426
Specifications:
MIL-W-19088 except as noted
Rating:
120 V ac, 5 amperes, 3 phases, 4 wire,
50/60 Hz
Scale:
250° ARC, white background with black
markings
Accuracy:
1.5%
Operating Temperature:
-25 to +125°F (-31 to 51°C)
Storage Temperature:
-65 to +155°F (-53 to 68°C)
Humidity Conditions:
To 100%
Manufacturer:
Westinghouse Electric Company
Part Number:
Style 3-81901 Type KP-241 with MV-832
phase shifter (meter must match phase
shifter)
FSCM:
88416
POWER FACTOR Meter M104
Drawing Number:
80-7425
Specifications:
MIL-M-16034 except as noted
Scale:
250° ARC, calibrated to read 0.5 pf
lag to 0.5 pf lead (cosine curve)
Movement:
+0.5 mA dc zero center
Operating Temperature:
-25 to +125°F (-31 to 51°C)
Storage Temperature:
-65 to +155°F (-53 to 68°C)
Humidity Conditions:
To 100%
Mechanical Characteristics:
Meter to be used in conjunction with
transducer 80-7382
Manufacturer:
General Electric Company
Part Number:
1014-3, Type DB-14
FSCM:
24493
SYNCHROSCOPE M106
Drawing Number:
80-7424
Specification:
MIL-I-16104, Type II, except as noted
Rating:
120 V ac, 5 amperes, single phase,
50/60 Hz calibrated at 55 Hz
Scale:
250 degrees ARC, white background
with black markings
Accuracy
+1.5%
Operating Temperature:
-25 to +125°F (-31 to 51°C)
Storage Temperature:
-65 to +155°F (-53 to 68°C)
Humidity Conditions:
To 100%
Manufacturer:
Westinghouse Electric Company
Part Number:
1-68248, Type KI-241
FSCM:
88416
1-34