ARMY TM 9-6115-60412
NAVY NAVFAC P-8-633-12
1.
SCREW AND CAPTIVE WASHER ASSEMBLY
23.
CHANNEL SUPPORT
2.
NUT AND CAPTIVE WASHER ASSEMBLY
24.
BAR SUPPORT
3.
DOOR HOLDER
25.
HEXAGON HEAD CAPSCREW
4.
SCREW AND CAPTIVE WASHER ASSEMBLY
26.
HEXAGONAL NUT
5.
NUT AND CAPTIVE WASHER ASSEMBLY
27.
LOCKWASHER
6.
DOOR ASSEMBLY
28.
FREQUENCY TRANSDUCER A103R
7.
HINGE
29.
LOAD GROUND TERMINAL
8.
RIVET
30.
RIVET
9.
RIVET TYPE RECEPTACLE
31.
IDENTIFICATION PLATE, GROUND
10.
SCREW AND CAPTIVE WASHER ASSEMBLY
32.
IDENTIFICATION PLATE, REMOTE CONTROL
11.
TERMINAL BLOCK TB1R MODULE
MODULE
12.
HORN
33.
HANDLE
13.
ELECTRICAL BOX
34.
CABLE ASSEMBLY
14.
GROMMET
35.
CONNECTOR COVER
15.
HEXAGON HEAD CAPSCREW
36.
RECEPTACLE CONNECTOR
16.
LOCKWASHER
37.
IDENTIFICATION PLATE J26R
17.
RUBBER BUMPER
38.
LEFT STORAGE BRACKET
18.
SCREW AND CAPTIVE WASHER ASSEMBLY
39.
RIGHT STORAGE BRACKET
19.
HEXAGON HEAD CAPSCREW
40.
REMOTE CONTROL BOX
20.
FLAT WASHER
41.
MOUNTING FLATWASHER
21.
SCREW AND CAPTIVE WASHER ASSEMBLY
42.
SELF-LOCKING WASHER
22.
NUT AND CAPTIVE WASHER ASSEMBLY
43.
DIODE
Figure 5-1. Remote Control Module Assembly (Sheet 2 of 2)
(2)
Connect the LOAD GROUND terminal (29) on the side of the remote control to a suitable ground.
(3)
Ensure that organizational maintenance personnel have performed the procedures described in
Chapter 4, Section I , "Service Upon Receipt of Equipment".
(4)
Ensure that before operation preventive maintenance checks and services have been performed on
the generator set.
(5)
Ensure that all shutters on the generator set are open and all doors on the generator set are closed.
(6)
Set LOCAL REMOTE switch S2 (23, Figure 2-2, Table 2-2) to REMOTE.
(7)
Set 24 V DC CONTROL POWER CIRCUIT BREAKER CB1 (2, Figure 2-1, Table 2-1) to ON.
(8)
Set MAINTENANCE LOCKOUT switch S100 (1, Figure 2-1, Table 2-1) to OPERATE.
(9)
Set OPERATION SELECTOR SWITCH S3 (21, Figure 2-2, Table 2-2) to MANUAL.
d.
Use of the RCM. Refer to paragraph 2-9.
5-4.
LUBRICATION. The remote control module requires no lubrication
5-5.
PREVENTIVE MAINTENANCE CHECKS AND SERVICES (A, N). To ensure that the remote control module is
ready for operation at all times, It must be Inspected systematically so that defects may be discovered and corrected
before they result in serious damage or failure. The necessary preventive maintenance services to be performed are
listed and described in Table 5-1 (A). Item numbers indicate the sequence of minimum inspection requirements.
Defects discovered during operation of the unit should be noted for future correction, to be made as soon as operation
has ceased. Stop operation immediately if a deficiency is noticed which could damage the equipment if operation were
continued. Record all deficiencies and short-comings together with the correct actions taken, on applicable form.
5-3