ARMY TM 9-6115-604-12NAVY NAVFAC P-8-633-12(2)High Fuel Level Switch FL4 High fuel level switch FL4 is mounted through the top of the generator set fueltank and is accessible through the floor of the control room FL4 will close on a high fuel condition toenergize self-latching relay A 10K6 in the annunciator alarm system. Horn LS1 sounds and annunciatorpanel light A9DS6 flashes while the generator set continues to run. A10K6 will energize high fuel levelfault slave relay K5. Relay K5 will open its normally closed contacts to deenergize fuel pump contactorK13. Transfer pump contactor K13 will open its normally closed contacts to cut off 120 V ac from fueltransfer solenoid L102 and fuel transfer pump contactor K106. Contactor K106 will deenergize, cutting off240 V ac from fuel transfer pump motor B102. Solenoid valve L102, deenergized will close to block thefuel inlet line, preventing any more fuel from entering the generator set fuel tank. This protection circuitprimarily prevents overfilling of the generator set fuel tank by gravity feed (siphoning) from the externalfuel supply. Secondarily, the circuit guards against fuel transfer system "runaway" which could occur ifhigh fuel level float switch FL2 failed to open upon a high fuel level condition.(3)Oil Pressure Alarm Switch OP2. Oil pressure alarm switch OP2 is mounted on the right end of the lubefilter head assembly. To allow time for oil pressure to build up in the engine block, the low oil pressurealarm circuit is not armed until 15 to 25 seconds after engine speed has exceeded 600 rpm. Oil pressurein the engine block causes the normally closed switch OP2 to open. If oil pressure should fall below 37 to41 psi (255 to 283 kPa) during engine operation, OP2 will close to energize self-latching relay A10K2.Annunciator horn LS1 sounds and annunciator panel light A9DS2 flashes while the generator set continuesto run. The operator is expected to investigate the cause of the low oil pressure warning. Generally, thecause will be insufficient crankcase oil in the engine. Failure to find and correct the cause of the warningmay result in a generator set shut down caused by oil pressure shutdown switch OP1.(4)Oil Pressure Shutdown Switch OP1. Oil pressure shutdown switch OP1 is mounted on the right end of thelube filter head assembly (OP1 and OP2 are in the same housing). To allow time for oil pressure to buildup in the engine block, the oil pressure shutdown circuit is not armed until 15 to 25 seconds after enginespeed has exceeded 600 rpm. Oil pressure in the engine block causes normally closed switch OP1 toopen. If oil pressure should fall below 28 to 32 psi (193 to 221 kPa) during engine operation, OP1 willclose to energize oil pressure shutdown relay K18. Relay K18 will energize fault shutdown relays K20Aand K20B Relay K20A deenergizes self-latching engine run relay K15B. As a result, engine fuel solenoidL1 loses power, closes, and cuts off fuel to the engine; the engine shuts down. Relay K20B energizescircuit breaker trip relay K30. Relay K30 energizes the trip coil in load circuit breaker CB101, opening thebreaker to disconnect generator G1 from the bus. The generator set cannot be restarted until theannunciator alarm system is reset via ANNUNCIATOR RESET pushbutton S12 on the upper door ofcabinet A.(5)Oil Temperature Switch OT2. Oil temperature switch OT2 is mounted on the left side of the engine oilpan. If the oil temperature in the engine sump rises to 242 to 248°F (117 to 120 C) or higher, the normallyopen switch OT2 will close to energize self-latching relay A10K4 in the annunciator alarm system.Annunciator horn LS1 sounds and annunciator panel light A9DS4 flashes.(6)Overspeed Switch SS3. Overspeed switch SS3 is connected to the tachometer drive of the engine fuelpump, which is located on the left side of the engine. Overspeed switch SS3 senses engine speed at alltimes. If engine speed uses above 2200 rpm, the normally open contacts of switch SS3 will close toenergize overspeed shutdown relays K19A and K19B. Relay K19A energizes fault shutdown relays K20Aand K20B and air shutdown solenoids L2A and L2B. Relays K20A and K20B shut down the generator setas described in step (4), above. Solenoids L2A and L2B close the air control valves to cut off air to theengine air intake manifolds. Relay K19B energizes self-latching relay A10K1 in the annunciator alarmsystem. Annunciator horn LS 1 sounds and annunciator panel light A9DS1 flashes. With both fuel and aircut off, the engine shuts down. Solenoids L2A and L2B remain energized only as long as engine oilpressure keeps normally open air shutdown solenoid disconnect switch OP3 closed. OP3 serves toautomatically deenergize solenoids L2A and L2B after the engine shuts down. This automaticdeenergization is required because solenoids L2A and L2B are not rated for continuous duty. Once anoverspeed fault shutdown occurs, the engine can be restarted only after the fault circuit is reset throughthe ANNUNCIATOR RESET switch on generator control cabinet A and the two air control valves mountednear the turbocharger are manually reset to the open positions and the speed switch button is reset.4-69
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business