ARMY TM 9-6115-464-34
AIR FORCE TO 35C2-3-445-2
NAVY NAVFAC P-8-624-34
3.
4.
5.
6.
7.
8.
9.
10.
INTERPRET DRAWING PER MlL-STD-100.
STACK LAMINATIONS, FIND NOS. 1 AND 2,
ON I.D. UNDER 2.5 ± 10% TONS.
BRAZE CAGE ROD, FIND NO. 3, TO
LAMINATIONS, FIND NO. 1, IN
ACCORDANCE WITH MILB-7883. TYPE 1,
GRADE B, BRAZING FLUX SHALL BE IN
ACCORDANCE WITH AWS TYPE 3A.
ONE COIL SPACER SHALL BE USED AT
EACH OF EIGHT PLACES.
APPLY 4 LAYERS OF TAPE, FIND NO. 8, TO
SECURE CABLE STUDS.
APPLY 2 1/2 LAYERS OF TAPE, FIND NO.
12, TO ROD, FIND NO. 4.
VACUUMPRESSURE IMPREGNATE IN
ACCORDANCE WITH 722487.
CLEAN CABLE STUDS AFTER
IMPREGNATION.
TORQUE CAP SCREWS, FIND NO. 5, TO
17FTLB ± 10% WHILE THE
LAMINATIONS ARE UNDER PRESSURE.
GROUND INSULATION: GREATER THAN
200 MEGOHMS.
HIGH POTENTIAL: 1500 VOLTS.
Figure 3-144. 50/60 Hz Generator, Rewinding Procedures
3-303