ARMY TM 9-6115-464-12AIR FORCE TO 35C2-3-445-1NAVY NAVFAC P-8-624-122-12 OPERATIONOFTACTICALUTILITYGENERATORSETS.a.Parallel Operation (Load Sharing).(1)(2)(3)(4)(5)(6)(7)(8)(9)The first set started shall be designated as “on-line” and the sets in parallel operation shall be desig-nated “on-coming”. With all sets shut down connect the load terminal boards as described in para-graph 2-4e. Check that the voltage reconnection boards (paragraph 2-5) of the sets are identicallypositioned.Do not place the circuit breaker switch on any of the generator sets in theCLOSE position until specifically directed to do so. Closing the circuitbreaker switch at any other time may severely damage one or more of thegenerator sets. Equipment damage could result if caution is not observed.Check that the main power switch (Figure 2-6) at the load is open before at-tempting to place a generator set on line. Equipment damage could resultif caution is not observed.Start the generator set as described in paragraph 2-6. Do not perform steps 7 & 8 of Figure 2-8.Hold the CKT BRK switch (30, Figure 2-1) of the “on-line” set in the CLOSE position until the CKTBRK indicator light (31) illuminates. Place the operation switch (26) in the PARALLEL position.Set “Volt-Amps Transfer Switch (5, Figure 2-1) in the L1 -L0 position. Adjust the voltage adjust rheo-stat (24) until the AC voltmeter indicates 122 volts for the 120/208 connection and 244 volts for the240/41 6 connection. Adjust manual speed control (21) until the frequency meter indicates 61 Hertz.Place the operation switch (26) of the “on-coming” set in the PARALLEL position.NOTEObserve the synchronizing lights of the “on-coming” set. The lights should go onand off simultaneously. If the lights go on and off alternately, sets are out of phase.Stop both sets and correct interconnect cables (Figure 2-5). If the problem per-sists, refer to next higher level of maintenance.Adjust the manual speed control of the “on-coming” set until the synchronizing lights (25), simulta-neously, remain on or off at 2 to 3 second intetvals.Carefully observe the synchronizing lights of the “on-coming” set and, at the instant both lights godark, place the CKT BRK switch (30) of the “on-coming” set to the CLOSE position. When the CKTBRK indicator light (31) illuminates, the sets are operating in parallel.With no external load on the paralleled sets, adjust the manual speed control (21) of the “on-coming”set until both percent power meters (kilowatt) indicate zero. Adjust the voltage adjust rheostat (24)of the “on-coming” set until the percent of rated current meters (ammeters) on both sets indicatezero. Turning counter clockwise will decrease readings.Apply load to the sets. The kilowatt load should divide so that the load on each set is equal. If theload and current are not shared equally, adjust the load by observing the set which has the higherreading on the kilowatt meter (4). Decrease the engine speed of this set by adjusting counter cloc-kwise the manual speed control (21 ) in small increments. Increase the engine speed of the set withthe lower kilowatt reading by adjusting clockwise the manual speed control in small increments. Ad-justments should be made between both sets until the kilowatt meters are balanced.The current should divide so that the observed difference between the current on any phase betweenthe “on-line” and “on-coming” sets is not more than 20 percent. If the readings are not within 20 per-cent, notify higher level maintenance.2-21
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business