TM 5-6115-593-12
TO 35C2-3-463-1
DC
Voltmeter
DOD Drawing Number ..... 76-11234
Scale .............................. 0 to 30V DC
Accuracy ......................... ± 2 percent
Frequency Meter
DOD Drawing Number ..... 69-595
Scale .............................. 48 to 53 Hz and
57 to 62 Hz; 250
degree scale
calibrated in Hz
from 48 to 62
Hz, scale
divisions of 0.1
Hertz
Input ............................... 120 volts, 1
phase 50/60 Hz
(matched with
frequency
transducer
69-578)
Fuel Level Gauge
DOD Drawing Numbe....... 69-575
Input ............................... 24V DC
Type ............................... Fuel, empty to
full, calibrated
1/4, 1/2, 3/4
Sender
resistance
. ........... Empty - 0 ohms,
1/2 full - 15
ohms, full - 30
ohms
Kilowatt Meter
DOD Drawing Number ..... 70-4012
Scale .............................. Percent power,
blue mark at 83
percent, red
mark at 100 per-
cent; full scale
0 to 133 percent
Accuracy ......................... 2 percent full
scale
Kilovar Meter
DOD Drawing Number ..... 76-11215
Type ............................... Percent kilovar
Scale .............................. Blue mark at 83
percent, red
mark at 100
percent, full
scale 0 to 133
percent
Lube Oil Temperature Gauge
DOD Drawing Number ..... 76-11228, used
with 76-11249
sender and
76-11230 resis-
tor for 24V DC
operation.
200°F (93°C)
- 548 ohms
300°F
(149°C) - 108
ohms
Scale .............................. 150 to 350°F
(100 to 150°C)
Lube Oil Pressure Gauge
DOD Drawing Number ..... 76-11227, used
with 76-11255
sender and
76-11230
resistor for 24V
DC operation.
0 psi - 240 ohms
80 psi - 60.3
ohms
Scale .............................. 0 to 100 psig
Oil Pressure Gauge
DOD Drawing Number..76-11104
Pressure range ......10 to 150 psi
(0.7 Jo 10.5
kg/cm
2
)
Mechanism ............................ C" shape bourbon
tube
Power Factor Meter
DOD Drawing Number ..... 76-11216
Power ............................. 120V AC
10 per-
cent, 50/60 Hz
Sensing Input ................. 0.25 to 5.0 amps
from current
transformer
Accuracy ........................
1 percent full
scale
Scale .............................. 7 inch, 250
degree
deflection
Time Totalizing Meter
DOD Drawing Number ..... 73-0507
Type ............................... Indicates total
hours of running
time
Scale .............................. 0 to 9999
Voltage Meter
DOD Drawing Number. ....
.69-599
Type ................. ..............
250 degree, 0 to
500 volt scale,
each scale,
division: 5
volts
Accuracy ........................ 2-1/2 percent of
full scale
(integral
rectifiers)
tor for 24 V DC
operation.
1-12