TM 5-6115-593-12
TO 35C2-3-463-1
(5)
If fuel tank is 1/2 full or more, jump
out contactor K20 (33, figure 4-17) by
momentarily
connecting
small
terminal A to large terminal P140C
with a jumper cable (see figure 4-32).
(6)
With 24V DC CONTROL CIRCUIT
BREAKER set ON, and the FUEL
PUMP switch in AUTO, check the flow
of fuel. It should pump approximately
1 gallon per minute (3.8 1 per
minute). Set FUEL PUMP switch to
OFF, flow should stop. Refer to next
higher maintenance if flow rate is not
met or pump fails to stop.
c.
Service. None required.
4-53.
FILTER AND STRAINER. (See figure 4-31).
a.
Removal.
(1)
Open drain cocks (23 and 29) on the
filter and strainer assembly (22).
(2)
Drain
the
fuel
into
a
suitable
container.
(3)
Remove
hose
connections
from
elbows (8) and (11) and remove
elbows.
(4)
Remove
four
screws
(20)
and
lockwashers (21) securing filter and
strainer assembly (22) to support
bracket (51). Remove filter and
strainer assembly (22).
(5)
Open drain cock (40) on
strainer assembly (39). (6) Drain the
fuel into a suitable container.
(7)
Remove
hose
connections
from
elbows (8), remove elbows.
(8)
Remove
four
screws
(37)
and
lockwashers (38) securing strainer
assembly to support bracket (51).
Remove strainer assembly (32).
b.
Replacement.
(1)
Install filter and strainer assembly (22)
on support bracket (51) with four
screws (20) and lockwashers (21).
(2)
Attach two elbows (8) and (11) to filter
and strainer assembly.
(3)
Attach hose connections to elbows.
(4)
Install strainer assembly (39) to
support bracket (51) with four screws
(37) and lockwashers (38).
(5)
Attach two elbows (8) to the strainer
assembly.
(6)
Connect hose to elbows (8).
(7)
Close drain cocks (23, 29, and 40).
NOTE
For filter and strainer servicing, refer
to paragraph 3-15.
4-89