TM 5-6115-593-12TO 35C2-3-463-1Table 4-3. Organizational Troubleshooting-ContinuedMALFUNCTIONTEST OR INSPECTIONCORRECTIVE ACTION9. GENERATOR OUTPUT VOLTAGE INCORRECT.Test VOLT ADJ switch S6 (88, figure 4-22) in accordance with paragraph 4-40.Replace VOLT ADJ switch S6 if defective (see paragraph 4-40).NOTEIf S6 is not defective, inspect motoroperated potentiometer B5 (4, figure 4-19) according toparagraph 4-35 and refer to next higher level of maintenance for testing.10. ENGINE WILL NOT START IN COLD WEATHERNOTEIf following procedures indicate cold weather starting devices are functioning, refer totroubleshooting procedures listed under ENGINE CRANKS AT NORMAL SPEED BUT WILL NOTSTART.Step 1.Refer to paragraph 4-65, and disconnect tubing from bottom end of ether kit assembly. Toggle STARTAID switch to ON position.WARNINGEther is highly flammable fuel. Do not expose to open flame, lit cigarettes, or hot surfaces.If ether is ejected out of opened end of ether kit assembly, perform inspection procedures inparagraph 3-19.If no ether appears, proceed to next step.Step 2.Test ether tank by shaking tank to determine if empty.If empty, replace with new ether tank.If there is still ether in tank, test START AID switch S2 (20, figure 4-21) and replace if defective(see paragraph 4-40).4-28