and current under load and varies the exciter field eitherup or down to keep the generator field at such a valueas to maintain constant alternator output voltage. Theregulated voltage setting can be varied using the voltageadjust rheostat (R1 ).On MEP-003A, an ac receptacle (J14 ) is connected througha protective circuit breaker (CB3) to provide 120 VAC.1-10.TABULATEDDATA.a. Identification and Instruction Plates (see figures 1-1and 1-2 ).(1) Identification Plate.(a) Location. This plate is located on the side ofthe control cubicle.(b) Content.US DEPARTMENT OF DEFENSEGENERATOR SET DIESEL ENGINE 10KW 60 HZMODEL: MEP-O03AGENERATOR SET DIESEL ENGINE 10KW 400HzMODEL: MEP-112ANSN: 6115-00-465-1030 (MEP-003A)NSN: 6115-00-465-1027 (MEP-112A)TM 5-6115-585-12TO-35C2-3-455-1NAVFAC P-8-623-12TM-05684C/05685B-12VOLTS: 120V 1PH.120/240V 1PH.120/208V 3PH.PF: 0.8AMPS: 104, 52,34.7DRY WT: 1220 LB (MEP-003A)DRY WT: 1325 LB (MEP-112A)LG: 62 INW: 32 INHGT: 37 INCONTR NO: F04606-74-C-1133 (MEP-003A)CONTR NO: DAAK70-78-C-0177 (MEP-112A)TM 5-6115-585-12NAVFAC P-8-623-12TO-35C2-3-455-1TM-05684C/05685B-12WARRANTY :DATE INSP :MFD BY: ONAN CORP.INSP STAMP:(2) Operating Instruction Plate.(a) Location. This plate is located on the side ofthe control cubicle.(b) Content.OPERATING INSTRUCTIONSBEFORE STARTING SET1. Insure output circuit breaker is off.2. Fill crankcase (do not overfill) and fuel tank.Ensure that vent on underside of fuel filler capis open before starting generator.3. “WARNING” – Ground set to avoid shock.hazard.4. Set batteries are negative ground.STARTING SET1.2.3.4.5.6.Move“MASTER SWITCH” to “PRIME &RUN” position to allow fuel to prime set.Move “MASTER SWITCH” to “PREHEAT”position end hold for (1) minute.NOTE: Preheat is not required when engine ishot.Move “MASTER SWITCH” to “START” posi-tion and hold until engine fires continuously.If engine does not start within 15 seconds,repeat steps 1 and 2.“MASTER SWITCH” will return to “PRIME &RUN” position when released. If running fromauxiliaryfuelsource,move“MASTERSWITCH” to “PRIME & RUN AUX FUEL”position.After warm up. Check frequency and voltageand adjust if necessary.M o v e " A C C i r c u i t B r e a k e r " t o " O N"position.STOPPING SET1.2.3.Move “AC CIRCUITposition.BREAKER” to “OFF”Move “MASTER SWITCH” to “OFF” position.For emergency stop Pull “DC CONTROLCIRCUIT BREAKER-.” -1 - 5Change 6
Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business