Table 1-1. Differences in Performance Characteristics
1. Voltage
(a)
(b)
(c)
(d)
Dip with application of
rated load.
Rise with rejection of
rated load.
Dip or rise with appli-
cation of simulated
motor load.
Adjustment range
2. Frequency
(a) Regulation.
(b) Short term steady state
stability.
(c) Long term steady state
stability.
(d) Undershoot with applica-
tion of rated load.
(e) Recovery after application
of rated load.
(f) Overshoot with rejection
of rated load.
(g) Recovery after rejection
of rated load.
(h) Drift (60° F change).
(i) Adjustment range
MEP006A
20% max.
20% max.
40% max.
50 Hz +2.5%
-10%
60Hz +15%
-5%
2 to 3%
Within
2% bandwidth
Within
3% bandwidth
3% max.
Within
3 seconds
4% max.
Within
3 seconds
1%
45-65 Hz
(Manual)
MEP105A
15% max.
15% max.
30% max.
50 Hz +2.5%
-10%
60Hz +15%
-5%
Within
± 0. 25%
Within
0.5% bandwidth
Within
1% bandwidth
1.5% max.
Within
1 second
1.5% max.
Within
1 second
0.5%
50 Hz
48 to 52 Hz
60 Hz
58 to 62 Hz
MEP115A
12% max.
12% max.
25% max.
400 Hz +10%
-5%
Within
±0.25%
Within
0.5% bandwidth
Within
1% bandwidth
1.5% max.
Within
1 second
1.5% max.
Within
1 second
0.5%
390 to 420 Hz
1-40