T O 35C2-3-442-2
P-8-627-34
TM-07464A-35 TM 5-6115-457-34
c. Repair damaged threads with a die
unsolder the leads from the connector (46)
or by filing with a fine mill file.
to the auxiliary contact assembly (51).
g. Remove nuts (52) and washer (53)
6-146E. REASSEMBLY. Refer to figure
from guide rod (55); carefully remove
6-36A and reassemble the main load con-
spring (55). Remove nuts (56) and washers
tactor as follows:
(57) and remove the post and operator (60),
core and rod assembly (59) and spacer (58)
a. Install switch bracket (69) and licon
from end plate (71).
switch (70) to end plate (71) using screws
(64 and 67), lock washers (65 and 68) and
h. Remove screws (61), lock washers
washers (66).
(62) and washers (63) from the core frame
(74). Carefully slide the core frame (74)
b. Insert coil washer (73) and coil (72)
containing the coil (72) and coil washer (73)
over center pin on coil frame (74). Care-
out from the end plate (71). Remove screws
fully align end plate (71) over the coil (72)
(64 and 67), lock washers (65 and 68) and
and coil frame (74). Place space (58), core
washers (66) and remove the switch bracket
and rod assembly (59) and post and opera-
(69) and licon switch (70) from the end plate
tor (60) onto end plate (71). Fasten post
(71).
and operator (60) to end plate (71) utilizing
guide rod (55), spring (74), nuts (52) and
washers (53). Install screws (61), lock
6-146B. CLEANING. Clean all components
washers (62) and washers (63) and tighten
with a clean lint-free cloth moistened with
snug. Install nuts (56) and lock washers
an approved cleaning solvent and dry thor-
(57) to the core and rod assembly (59).
oughly .
WARNING
6-146C.
INSPECTION.
Avoid breathing fumes generated by
tection is required.
a. Inspect harness wiring for defective
c. Connect and solder electrical leads
from connector (46) to auxiliary contact
b. Inspect harness connector for dam-
assembly (51). Install actuator assembly
aged threads; bent, loose or missing pins
(45) to end plate (71) and core frame (74)
and for shorts.
using screws (47 and 49) and washers (48
and 50). Carefully clamp post and operator
c. Check electrical components for
(60) and the core frame (74), so that no air
space exists between the coil (72) and the
values.
core and rod assembly (59). Also check
that no air space exists between the spacer
(58) and end plate (71). Tighten screws
6-146D. REPAIR,
(47 and 61). Remove the clamp and insert
a .150. 010, feeler gage, between the coil
a. Replace contactor coil (72, figure
(72) and core and rod assembly (59). Ad-
6-36A) if defective.
just the guide rods (55) until the gage is
snug. Secure after adjustment by tightening
b. Replace contacts if badly pitted or
nuts (52).
burned.
Change 8
6-118