P-9-TM-457-35 T.O. 35 C2-3-442-2
TM-07464A-35 TM 5-6115-457-34
Isochronous 1/4 of 1 percent.
Frequency Regulation
Short Term
(30 Seconds)
Long Term
(4 Hours)
rated frequency.
1/2 of 1 percent.
Frequency Drift
(8 Hours)
Transient performance
(application or rejection
of load).
Stable Operation
within 2 seconds.
Overshoot or
4 percent of rated frquency
Undershoot
Weight
3 pounds (approx.)
Overall dimensions
6.00 x 3.80 x 4.38 inches (approx.)
f. GENERATOR
DOD Drawing Number
Manufacturer
Lima Electric Motor Company
Type
2 Types: 50/60 Hertz or 400 Hertz.
Both are synchronous, brushless,
Operating Speed:
50 Hertz
1500 RPM
60 Hertz
1800 RPM
400 Hertz
2000 RPM
Kilowatt Rating (KW):
(At 0.8 P. F.)
83.3
50 Hertz
60 and 400 Hertz
100
1-18