TM 5-6115-400-12
and installation.
Figure 3-63 (2)--Continued.
Section XVII. WINTERIZATION EQUIPMENT
3-83. General
110V, 50/60 or 400 CPS power supply. Refer to
supplement to this manual for operation and
Winterization equipment, for starting the engine when
maintenance of this auxiliary kit.
temperatures are below -25F., consists of two kits as
follows:
3-84. Heaters
a. A generator set kit including two heaters,
a. Removal and Installation.
coolant lines, fuel line, electrical controls, and mounting
hardware to be installed in the set for preheating the
engine oil pan and cooling system. The heaters are
designed to use a variety of fuels and can be operated
(1)
Turn fuel valve to OFF position.
on any fuel available from the diesel engine fuel system.
(2)
Turn both coolant valves to OFF position.
(3)
Disconnect electrical connectors from heaters.
b. A portable auxiliary winterization kit is also
(4)
Disconnect fuel line from heater.
available to provide separate heated and charged
(5)
Disconnect coolant lines from heater.
batteries. This kit includes a heater for heating the
auxiliary batteries and a battery charger which can be
(6)
Remove mounting clamps and remove heaters.
connected to any
3-64