Operator Preventive Maintenance Checks and Services - continued - TM-9-6115-660-13P_51
Operator Preventive Maintenance Checks and Services - continued - TM-9-6115-660-13P_53

TM-9-6115-660-13P Power Plant Diesel Engine Driven 1-Ton Trailer Mounted (With Racks) 3Kw 60 Hz AN/MJQ-42 Manual
Page Navigation
  22    23    24    25    26  27  28    29    30    31    32  
TM 9-6115-660-13&P Table 2-2.  Operator Preventive Maintenance Checks and Services - continued Location Item Interval Procedure Not Fully Mission No. Item to Capable if: Check/Service 18 Before ACOUSTICAL Ensure acoustical materials, located in the MATERIAL grill areas and under the engine, are secure, not damaged, or missing. 19 Before    ENGINE Check for loose or damaged hardware. ASSEMBLY 20 Before FUEL SYSTEM Inspect for leaks, damaged, loose, or Any fuel leaks, missing hardware damaged, loose, or missing parts. 21 Before FUEL FILTER/ a Inspect fuel filter/water separator (34) Any fuel leaks. WATER and fuel filter (35) for leaks, proper SEPARATOR mounting, cracks, damage, or missing parts. WARNING With  any  access  door  open,  the  noise  level  of  this  generator  set  when  operating  could  cause  hearing damage.  Hearing protection must be worn when working near the generator set while running. WARNING The  fuels  used  in  this  generator  set  are  highly  explosive.    Do  not  smoke  or  use  open  flame  when performing maintenance.  Flames and explosion can occur resulting in severe personal injury or death. 2-18  Change 2