TM  9-6115-660-13&P 4-16  TOGGLE  SWITCH  MAINTENANCE. This  task  covers:  a.  Test c. Installation b.  Removal INITIAL  SETUP Tools Equipment   Conditions Tool  Kit,  General  Mechanic’s (item 1, appendix B) Reference Multimeter  AN/PSM-45 Both generator sets shut down; (item 2, appendix B) paragraph  2-5.3.3. Switch  box  cover  open. Materials/Parts None TEST NOTE The following procedures apply to  all  toggle  switches. Set  multimeter  for  continuity  test.  Test  switches  in  accordance  with  table  4-3.  Replace  any  switch  that fails test. Table  4-3.  Switch  Continuity  Test S10 TRANSFER SWITCH S1 AND S2 ON-LINE SWITCHES Closed  Contact Open   Contact Closed  Contact Open  Contact On Position 1 and 2 2 and 3 4 and 5 5 and 6 Released 1 and 2 2 and 3 5 and 6 Position 4 and 5 REMOVAL 1. Tag wires connected to terminals of switch to be replaced and remove screws (9, figure 4-16), flat washers (8), and conductor bus (7). 2. Remove hex nut (1), lock washer (2), locking ring (3), and switch 6. INSTALLATION 1. 2. Remove hex nut (1), lock washer (2), and locking ring (3). Hand tighten hex nut (5) on switch. 4-32