Section VI.  MAINTENANCE PROCEDURES.
Figure 4-11. Disconnect Power Cable from Generator Set. - TM-9-6115-660-13P_113

TM-9-6115-660-13P Power Plant Diesel Engine Driven 1-Ton Trailer Mounted (With Racks) 3Kw 60 Hz AN/MJQ-42 Manual
Page Navigation
  80    81    82    83    84  85  86    87    88    89    90  
TM 9-6115-660-13&P 4. 5. Figure 4-10. Power Cable Connections to Switch Box Contactors. Use multimeter to check for shorts in power cable. Check for continuity between ground and L0, L1, L2, and L3; L0 and L1, L2, and L3; L1 and L2, and L3; and L2 and L3. Continuity in any of these tests indicates a shorted cable which must be replaced. Close switch box cover (1) and secure with clamping catches (11). REMOVAL 1.  Disconnect  electrical  leads  and  ground 2.   Pull power cable from stuffing tube. lead  from  generator  set. a. Remove stuffing tube compression nut (8, figure 4-11) from stuffing tube body (11). 4-20