• Home
  • Download PDF
  • Order CD-ROM
  • Order in Print
WARNING - TM-9-6115-464-34_67
BATTERY CHARGING ALTERNATOR - TM-9-6115-464-34_69

TM-9-6115-464-34 Generator Set Diesel Engine Driven Tactical Skid Mtd 15 Kw 3 Phase 4 Wire 120/208 and 240/416 Volts Manual
Page Navigation
  46    47    48    49    50  51  52    53    54    55    56  
ARMY TM 9-6115-464-34 AIR FORCE TO 36C2-3-445-2 NAVY  NAVFAC  P-8-624-34 f. Assembly. (1) Assemble starter and solenoid in reverse order of disassembly procedures using new gaskets and o-rings. Inspect all insulating washers and bushings. Replace if defective. (2) If brushes were replaced, run in new brushes as follows: (a) Cover armature commutator with a piece of No. 00 grit sandpaper. (b) Temporarily install brushes and commutator end frame and run in brushes. (c) Disassemble, remove sandpaper, and clean armature commutator and brushholder assembly with filtered compressed air. g. Testing. (1)  Test  starter  solenoid  assembly  as  follows: (a)  Remove  connector  (14,  Figure  3-4). (b) Apply 24 Vdc between the negative terminal and the small terminal of the solenoid assembly. (c) Solenoid actuation will be indicated by an audible “click” and rearward movement of the drive gear. (d) Remove 24 Vdc from solenoid assembly terminals. (e) The drive gear should move forward with an audible click. (f) Replace solenoid assembly if it fails to function properly. (g)  Install  connector. (2)  Conduct  starter  assembly  motoring  test  as  follows: (a)  Remove  connector  (14,  Figure  3-4). (b) Install starter assembly into motoring test circuit shown in figure 3-2. (c) Adjust rheostat until voltmeter indicates 22.5 volts. (d)  Check  indications  of  ammeter  and  tachometer. (e) Ammeter should indicate 58 amperes maximum with starter turning at 9300 rpm. (f) If current and speed are low, disassemble starter and check for high resistance at internal connection. (g) If current is high and rpm low, disassemble and inspect armature shaft and bushings for wear or misalignment. (h) Do not install connector (14, Figure 3-4) until stalled torque test is completed. (3)  Conduct  starter  assembly  stalled  torque,  test  as  follows: CAUTION Rheostat must have a minimum capacity of 1000 amperes. Failure to observe this caution could result in equipment damage. (a) Install starter assembly in test setup shown in figure 3-3. (b) Adjust rheostat until voltmeter indicates 14 Vdc. 3-14







Western Governors University

Privacy Statement
Press Release
Contact

© Copyright Integrated Publishing, Inc.. All Rights Reserved. Design by Strategico.