CAUTION - TM-9-6115-464-34_390
FREQUENCY ADJUST RANGE TEST

TM-9-6115-464-34 Generator Set Diesel Engine Driven Tactical Skid Mtd 15 Kw 3 Phase 4 Wire 120/208 and 240/416 Volts Manual
Page Navigation
  365    366    367    368    369  370  371    372    373    374    375  
ARMY TM 9-6115-464-34 AIR FORCE TO 35C2-3-445-2 NAVY  NAVFAC  P-8-624-34 Trace and definitions apply to either voltage or frequency. NOTE Chart marked at start of test. A      Actual  instrument  trace  of  function. B  Observed steady–state band (two lines parallel to the axis of chart movement one each passing through the center points of maximum and minimum trace excursion  respectively  during  the  short- term  stability  sample  period,  TS). C   Mean of observed band. CL Mean value at selected load. CN Mean value at no load. D   Prescribed steady-state band. E   Point at which trace initially leaves prescribed load band under condition of decrease in load. F Point at which trace enters and remains within  prescribed  no  load  band. G Point at which trace initially leaves prescribed no load band. ,H Point at which trace enters and remains within  prescribed  load  band. R  Regulation between any two loads. S    Surge  after  a  load  charge. SO   Overshoot SU  Undershoot TFL  Observed recovery time, no load to load. TFN  Observed recovery time, load to no load. TG Maximum allowable recovery time. TGL Maximum allowable recovery time, no load to load. TGN  Maximum  allowable  recovery  time,  load to no load TS  Prescribed  short-term  sample  time  for determining  stability. Figure 4-1. Overshoot and Undershoot Chart Recording 4-14







Western Governors University

Privacy Statement
Press Release
Contact

© Copyright Integrated Publishing, Inc.. All Rights Reserved. Design by Strategico.