WATER  PUMP
Asssembly

TM-9-6115-464-34 Generator Set Diesel Engine Driven Tactical Skid Mtd 15 Kw 3 Phase 4 Wire 120/208 and 240/416 Volts Manual
Page Navigation
  104    105    106    107    108  109  110    111    112    113    114  
ARMY TM 9-6115-464-34 AIR FORCE TO 35C2-3-445-2 NAVY  NAVFAC  P-8-624-34 Figure  3-28.  Water  Pump  Assembly,  Exploded  View (1) (2) (3) (4) (5) (6) (7) (8) WARNING Solvent, Dry Cleaning P-D-880, Type II is flammable and moderately toxic to skin, eyes and respiratory tract. Eye and skin protection required. Good general ventilation is normally adequate. Failure to observe this warning could cause servere personal injury. Clean all parts in dry cleaning solvent (Federal Specification P-D-680) and dry thoroughly. Visually inspect cooling fan pulley for cracks, corrosion, and excessive wear. Check pulley hub for cracks, corrosion, and other damage. Inspect cover plate for cracks, corrosion, and rub marks on inner face. Inspect pump body for cracks, breaks, and excessive wear. Inspect shaft and bearing assembly for deep wear patterns, scores, pitting and other damage. Rotate bearing on shaft. If bearing is binding or feels rough, the shaft and bearing assembly must be replaced. Check impeller for erosion, cracking, and other damage. Replace any damaged or defective parts. 3-73 c.   Cleaning,   Inspection   and   Repair